Horizontal Rackmount Remote Power Manager - 208-240-VAC, Dual-Circuit, (8) IEC-320-C13 Outlet
Product Features
Reboot remote servers, routers, Web cams, firewalls, and other devices from your home or office. Control devices via Telnet over a TCP/IP network, a Web browser and a modem, or serial commands.
Control devices via Telnet over a TCP/IP network, a Web browser and a modem, or serial commands.
ncludes SNMP control (v1, v2c, v3), SSHv2 encryption, and an SSL Web browser (https) for setup and operation.
Horizontal configuration.
Feature individually controllable outlet plugs.
This model is for 208 - 240-VAC equipment; versions are also available for 105 - 120 VAC, 100 - 120 VAC, and 100 - 125 VAC.
Two levels of password protection and encrypted 64-bit password security.
Only authorized users can make configuration changes.
An RS-232 port is for modem or console connections. A 10BASE-T interface provides network connections.
Takes up only 1U of space.
Models with dual power circuits are also available.
No more traveling to reboot your equipment in the middle of the night! No more service calls just to flip a switch! This Black Box® Rackmount Remote Power Manager enables you to reboot up to 8 network devices from across your network, by modem, with Telnet, or even from the Internet.
Just type the power manager's IP address into your Web browser, enter your name and password, and you can access your network devices to switch them on, switch them off, or reboot. The power managers are perfect for remotely rebooting servers, routers, network switches, Webcams, firewalls, and many other network devices.
The Web browser interface works across any TCP/IP network - even the Internet - with any JavaScript-enabled Web browser. Its intuitive interface features easy-to-use menus. Control power by plug number or by name (such as ATM Switch 1, Gateway, Router 1, etc.) that you assign to each outlet.
You can also operate the Horizontal Rackmount Remote Power Manager through an ASCII command-line interface via Telnet™ over a TCP/IP network, through a modem connection, or from a local PC using a terminal emulator.
Horizontal Rackmount Remote Power Managers have built-in password security to prevent unauthorized users from switching your devices or changing your configuration. Both the Web browser and the command-line interface use 64-bit encryption.
Two levels of operational passwords provide an additional layer of security: System-level passwords provide access to all configuration and switching functions. The user-level limits switching to assigned plugs and cannot be used to change the power manager configuration.
Horizontal Rackmount Remote Power Managers feature an IP-addressed 10BASE-T interface for network connections and an RS-232 port for modem or console connections.
General
Data Format Serial ASCII, 7/8 bits, no parity, 300 bps-38.4 kbps
Operating Environment Temperature: 32 to 122° F (0 to 50° C); Humidity: 10 to 90% noncondensing
Power AC input: 208-240 VAC, 50/60 Hz, 10 amps maximum per circuit; AC output: (8) plugs split into (2) 10-amp circuits with Power Circuit A (Plugs 1-4) and Power Circuit B (Plugs 5-8) supporting a load of 20 amps total
Protocol HTTP, Telnet, RS-232
User Controls (1) manual control button, (2) circuit breakers
Item Specifications
Connectors RS-232C: (1) DB9 (Male) (DTE); Network: (1) RJ45 (10BASE-T Ethernet); AC Input: (2) IEC 320-C20 inlets; AC Output: (8) IEC 320-C13 outlets
Dimensions 1.75"H x 19"W x 7"D (4.4 x 48.3 x 17.8 cm)
Weight 10 lb. (4.53 kg)
* Technical specification weight is the unit weight. It is not the packaged shipping weight.